局部排氣導管設計
基本假設 非壓縮性流,流體密度不變,質量守恆→風量(流量)守恆 導管無洩漏
造成靜壓變化的因素 管壁摩擦(同時造成全壓損失) 紊流(同時造成全壓損失) 流速改變(不造成全壓損失)
管壁摩擦
紊流壓損 DPS= F PV < 0
流速改變 靜壓下降 全壓幾乎不變
導管開口(含氣罩)的壓力損失 風速:0 -> 導管風速 動壓:增加 若無其他損失: 考慮摩擦與紊流損失 靜壓下降:且下降量 = 動壓增加量 全壓不變 考慮摩擦與紊流損失 全壓下降 靜壓下降,且下降量 > 動壓增加量
若無摩擦與紊流損失 Pv = 25 mmH2O Ps = -25 mmH2O Pt = 0 考慮摩擦與紊流損失 Ps = -40 mmH2O Pt = -15 mmH2O v = 20 m/s Pv Ps = 0 Pv = 0 Pt = 0 Pt Ps
描述氣罩壓力損失的方法 壓損因數(Entry Loss Factor,Fh) 進口係數(Coefficient of Entry,Ce)
氣罩壓損係數 氣罩後方 Pt = -Fh Pv or DPt = Fh Pv Ps = Pt –Pv = -Fh Pv –Pv = -(Fh + 1) Pv or DPs = (1 + Fh )Pv 1 :加速因數
若無摩擦與紊流損失 Pv = 25 mmH2O Ps = -25 mmH2O Pt = 0 考慮摩擦與紊流損失 Ps = -40 mmH2O Pt = -15 mmH2O Fh = -Pt/Pv = 15/25 = 0.6 or = -Ps/Pv – 1 = 40/25 – 1 = 0.6 v = 20 m/s Pv Ps = 0 Pv = 0 Pt = 0 Pt Ps
氣罩進口係數 Ce = 氣罩風量/無壓損之流量 = Q/Qmax
若無摩擦與紊流損失 Pv = 25 mmH2O Ps = -25 mmH2O Pt = 0 考慮摩擦與紊流損失 Ps = -40 mmH2O Pt = -15 mmH2O v = 20 m/s Pv Ps = 0 Pv = 0 Pt = 0 Pt Ps
氣罩前後壓力變化 Fh Pv Ps = (1+Fh) Pv Pt = Fh Pv Ce
如何決定壓損係數 自行測試(壓力計,建議採用) 廠商提供資訊 經驗公式或圖表(最後手段)
風量 壓 力 損 失 風速 壓 力 損 失 DPt = K×Q2 v = Q/A 壓 力 損 失 Pv = rv2/2 DPt = F×Pv 動壓
局部排氣導管設計基本要求 每一氣罩風量須高於需求值 每一導管風速須高於搬運風速 其他考慮因素: 導管內物質濃度 風速上限:靜電、管壁摩耗、物料損失 出口排放風速 排氣機進出口管徑
如何決定氣罩風量 法令要求:控制風速與抑制濃度要求 作業人員個人採樣 煙霧測試或追蹤氣體 方法: 測試(建議採用) 圖表或經驗公式
log(氣罩設計風量) log(氣罩風量) log(容許濃度) log(個人採樣濃度)
如何決定搬運風速 污染物 愈濕黏 搬運風速 愈大
導管設計主要目的 決定各導管管徑 決定排氣機性能要求
例題 具單一氣罩之局部排氣裝置 氣罩風量:8.5 m3/min 氣罩壓損係數:Fh = 0.85 氣罩至排氣機導管: 排氣機至出口導管 搬運風速:23 m/s 以上 含有一肘管(Fe = 0.22) 排氣機至出口導管 長度:2.4 m 直徑:10 cm
Pt0 = Pv0 = Ps0 = 0 Ps4 = 0 2 3 4 1 2.4 m 11.6 m 計算方向 計算方向 空氣密度 r = 1.2 kg/m3 氣罩風量需求:Q = 8.5 m3/min 氣罩壓損係數:Fh = 0.85 肘管壓損係數:Fe = 0.22 排氣機前導管最低搬運風速:vmin = 23 m/s 排氣機後導管管徑:10 cm 導管摩擦損失因數 f = 0.024
0-1 Q = (8.5 m3/min)(1 min/60 s) = 0.1417 m3/s 導管截面積最大為:Amax = Q/vmin = (0.1417 m3/s)/(23 m/s) = 0.006159 m2 若導管截面積大於此值,導管內風速會小於規定的 23 m/s 導管最大管徑 dmax = (4Amax/p)1/2 = [(4)(0.006159 m2)/p]1/2 = 0.08856 m Amax = pdmax2/4
0-1(續) 若導管管徑只能使用 2、3、4、…cm:取管徑 d1 = 8 cm = 0.08 m 若以四捨五入取 d1 = 9 cm > dmax,會使導管內風速小於規定的 23 m/s 若導管管徑可以訂做(自由選取),則令 d1 = dmax = 0.08856 m 若管徑 d1 已事先給定,則無需上述步驟
0-1(續) 以管徑 d1 = 0.08 m 繼續以下計算: 導管截面積:A1 = pd12/4 = p (0.08 m)2/4 = 0.005027 m2 v1 = Q/A1 = (0.1417 m3/s)/(0.005027 m2) = 28.18 m/s > vmin = 23 m/s Pv1 = rv12/2 = (1.2 kg m/s)(28.18 m/s)2/2 = 476.6 Pa 在 20°C 時,若要求單位為 mmAq,則可使用 Pv1 = (28.18/4.04)2 = 48.7 mmAq
0-1(續) 氣罩壓損:DPth = Fh Pv1 = (0.85)(476.6 Pa) = 405.1 Pa 氣罩後方(點 1): 氣罩後方導管動壓 氣罩壓損:DPth = Fh Pv1 = (0.85)(476.6 Pa) = 405.1 Pa 氣罩後方(點 1): Pt1 = 0 – DPth = -405.1 Pa Ps1 = Pt1 – Pv1 = -405.1 Pa – 476.6 Pa = -881.7 Pa 或 Ps1 = -(1 + Fh) Pv1 = (1 + 0.85)(476.6 Pa) = -881.7 Pa acceleration factor
1-2 導管壓損:f(L12/d1)Pv1 = (0.024)(11.6 m)/(0.08 m)(476.6 Pa) = 1659 Pa 肘管壓損:FePv1 = (0.22)(476.6 Pa) = 104.9 Pa 1-2 的總壓損 DPt1-2 = 1659 Pa + 104.9 Pa = 1763 Pa 通式:DPt1-2 = (fL12/d1 + SF)Pv1 =[(0.024)(11.6)/(0.08) + 0.22](476.6 Pa) = 1763 Pa = DPs1-2 導管上配件壓損係數總和 導管摩擦壓損係數 A1 = A2,v1 = v2 ,Pv1 = Pv2,DPt 1-2 = DPs1-2
1-2(續) 排氣機入口(點 2): Pv2 = Pv1 = 476.6 Pa Pt2 = Pt1 – DPt1-2 = -401.5 Pa – 1763 Pa = -2168 Pa Ps2 = Pt2 – Pv2 = -2168 Pa – 476.6 Pa = -2645 Pa 或 Ps2 = Ps1 – DPs1-2 = -881.7 Pa – 1763 Pa = -2645 Pa
4-3 排氣機後方導管:由出口往前算 排氣機後方導管管徑已給定: d3 = d4 = 10 cm = 0.1 m A3 = A4 = pd42/4 = pd32/4 = p (0.1 m)2/4 = 0.007854 m2 v3 = v4 = Q/A3 = Q/A4 = (0.1417 m3/s)/(0.007854 m2) = 18.04 m/s Pv3 = Pv4 = rv32/2 = rv42/2 = (1.2 kg/m3)(18.04 m/s)2/2 = 195.2 Pa
4-3(續) 出口(點 4) 導管 3-4 壓損: Ps4 = 0(大氣) Pt4 = Ps4 + Pv4 = 0 + 195.2 Pa = 195.2 Pa 導管 3-4 壓損: DPt3-4 = fL34/d3 Pv3 = (0.024)(2.4 m)/(0.1 m)(195.2 Pa) = 112.4 Pa = DPs3-4 A3 = A4,v3 = v4 ,Pv3 = Pv4,DPt 3-4 = DPs3-4
4-3(續) 排氣機出口(點 3) Pt3 = Pt4 + DPt3-4 = 195.2 Pa + 112.4 Pa = 307.7 Pa Ps3 = Pt3 – Pv3 = 307.3 Pa – 195.2 Pa = 112.4 Pa 其實就是 DPs3-4 ,因為 Ps3 = Ps4 + DPs3-4 = 0 + DPs3-4
Pv Pt FTP Ps FSP
FTP 與 FSP 排氣機全壓(FTP) = 排氣機出口全壓 – 排氣機入口全壓 = Pt3 – Pt2 = 307.7 Pa – (-2168 Pa) = 2476 Pa 用來計算耗電量 排氣機靜壓(FSP): = FTP – 排氣機出口動壓(Pt3 – Pt2 – Pv3) = 排氣機出口靜壓 – 排氣機入口全壓(Ps3 –Pt2)= 112.4 Pa – (-2168 Pa) = 2281 Pa 排氣機標準規格(可以提高多少壓力) FTP
排氣機耗電量 總效率 h P = (0.1417 m3/s)(2476 Pa)/0.4 = 877 W = 0.877 kW 每運轉一小時耗電 0.877 度
系統需求曲線 FSP ≈Q2 設計點: FSP = 2281 Pa @8.5 m3/min 排氣機風量