动态单线图显示 用于综合管理及 保护控制 Sepam 80系列 高端产品 用于全面应用方案 Sepam 40系列: 高性能 用于特别应用方案 Sepam 20系列: 经济型 用于普通应用方案 Sepam F20: 经济型 用于一般馈线 Sepam range: - Sepam series 20, simple solutions for common applications low-end protection relays, which fully replaces the Sepam 1000 range - Sepam series 40, high-performing solutions for demanding applications mid-range protection relays - Sepam series 80, intelligent solutions for complete applications high-end protection relays with differential protection and large number of I/Os NB: the Sepam 2000 range remains available for the applications not performed by the Sepam series 20/40/80: - customized control functions, programed thanks to Logipam - differential protection of 3-winding transformers - synchro check - busbar and capacitor applications

3 Sepam Merlin Gerin 格守精准定律,引领方向如一!
Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

4 Sepam 保护继电器, 格守精准定律, 引领方向如一!
功能选型 模块化结构 产品特点 方案与应用 2

5 Sepam 选型指南

6 出线保护应用 Sepam F20 保护功能: 50/51, 2段相过流(过流、速断), 50N/51N, 2段接地故障保护 电流测量
4个输出口 无通讯功能 Simple solution for common substation applications: protection of cable incomers and feeders or substation lines Sepam S20 type, with the following protection functions: 50/51: protection against phase-to-phase short-circuits (see "performance" for details) 50N/51N: protection against phase-to-earth short-circuits (see "performance" for details) 46: protection against phase unbalance (or phase loss) which causes overheating and deterioration of the equipment supplied Measurement of phase currents and residual current Logic discrimination: used to reduce fault (short-circuit) tripping time and thereby reduce the consequences. Discrimination principle based on the exchange of logic data between downstream and upstream protection units 4-cycle recloser: interests energy distributors rather than industrialists, to eliminate transient faults affecting overhead lines. -> Reduction of breaking time

7 进出线保护应用 Sepam S20 保护功能: 50/51, 4段相过流(过流、速断…), 50N/51N, 接地故障保护
46, 负序 / 不平衡 逻辑分辨 4次重合闸 电流测量 Simple solution for common substation applications: protection of cable incomers and feeders or substation lines Sepam S20 type, with the following protection functions: 50/51: protection against phase-to-phase short-circuits (see "performance" for details) 50N/51N: protection against phase-to-earth short-circuits (see "performance" for details) 46: protection against phase unbalance (or phase loss) which causes overheating and deterioration of the equipment supplied Measurement of phase currents and residual current Logic discrimination: used to reduce fault (short-circuit) tripping time and thereby reduce the consequences. Discrimination principle based on the exchange of logic data between downstream and upstream protection units 4-cycle recloser: interests energy distributors rather than industrialists, to eliminate transient faults affecting overhead lines. -> Reduction of breaking time

8 进出线保护应用 Sepam S40/S41/S42 可应用于各种中性点不接地或接地网络 d 保护功能:
50/51(相过流), 50N/51N(接地),46(负序不平衡),50BF(断路器失灵) 67N/67NC, 方向性接地故障-S41/S42 27/59,欠电压/过电压 81L/81H,欠频/过频 67, 方向性过流保护-S42 32P, 方向性有功过功率-S41/S42 I, U, P, E 测量 High-performing solutions for demanding substation applications: protection of networks/substations with: - parallel incomers (67/32P), in a closed ring (67) - isolated or compensated neutral (67N/67NC) Sepam S40/S41/S42 type, with the S20 protection functions, plus: 67N/67NC: directional earth fault protection (see "performance" for details) 67: directional phase overcurrent protection (see "performance" for details) 32P: directional power protection (see "performance" for details) 50BF: detection of breaker failure to quickly isolate the faulty part of the network by tripping the adjacent breakers (faster than natural tripping by upstream protection units) Voltage and frequency protection functions: 27/59: under/overvoltage, 81L/81H: under/overfrequency 59N: neutral voltage displacement, to detect/indicate earth faults on isolated neutral networks 47: checking of phase rotation direction, based on calculation of positive sequence voltage Logic discrimination for fast, selective tripping and switching of groups of settings for effective protection of variable-configuration networks (to be sensitive to very different fault currents according to the network configuration) S42 type especially designed for protection of closed ring: emission and reception of 2 separate blocking orders, in association with 67 and 67N/67NC. 4-cycle recloser Measurement of phase and residual currents, phase-to-neutral and residual voltages

9 进出线保护应用 Sepam S80/S81/S82 全面的控制功能 (42I/23O) 保护功能:
50/51(相过流), 50N/51N(接地),46(负序不平衡),50BF(断路器失灵) 67N/67NC(方向性接地故障), 32P(方向性有功过功率) -S81/S82 67 (方向性接地故障) -S82 27/59(欠/过压), 81L/81H(欠/过频) 49RMS (主电缆热过载) -S81/S82 I, U, P, E 测量 Intelligent solutions for complete substation applications: protection of networks/substations with: - parallel incomers (67/32P), in a closed ring (67) - isolated or compensated neutral (67N/67NC) - large number of I/Os and logical equation editor => integral equipment control Sepam S80/S81/S82 type, with the S40/S41/S42 protection functions, plus: 49RMS cable: Cable thermal overload, to protect the main cables between substations, without transformers Same principle as thermal overload for transformers or machines with simplified settings adapted to the cable application. 27D: Positive sequence undervoltage, to detect insufficient or unbalanced network voltage 27R: Remanent undervoltage, to allow the busbar supplying motors to be re-energized Logic discrimination for fast, selective tripping and switching of groups of settings for effective protection of variable-configuration networks (to be sensitive to very different fault currents according to the network configuration) S82 type especially designed for protection of closed ring: emission and reception of 2 separate blocking orders, in association with 67 and 67N/67NC. 4-cycle recloser Measurement of phase and residual currents, phase-to-neutral and residual voltages

10 进出线保护应用 Sepam S84 进线/出线含甩负荷功能的保护 甩负荷功能 81L(欠频), 4 个继电器
81R(频率改变率), 2个继电器 保护功能 50/51, 67, 49RMS 50N/51N, 67N/67NC, 59N 49 RMS, 电缆热过载 I, U, P, E测量 Sepam S84 for load shedding Role of the 81R function in a frequency-based load-shedding system: - either accelerate load shedding for the first group of feeders, - or, on the contrary, inhibit load shedding if power is lost or remanent voltage is sustained by motors. A single S84 function (generally for incomer protection) is sufficient to detect those cases where load shedding is necessary and send the shedding orders to the other Sepam units via the logic outputs.

11 变压器保护应用 Sepam T20 保护功能: 50/51(相过流), 50N/51N(接地),46(负序不平衡) 49RMS, 过负荷
非电量保护:超温报警/高温跳闸,轻瓦斯报警/重瓦斯跳闸 I 电流测量 Simple solution for common transformer applications: protection of an incomer or feeder transformer. Sepam T20 type, with the Sepam S20 protection functions, plus: 49RMS: thermal overload protection against transformer overloads based on the measurement of RMS currents (unfiltered RMS current up to harmonic 17) 38/49T: temperature monitoring, based on the measurement of temperatures at different points in the transformer. (typically 1 temperature sensor per primary+secondary transformer winding, a maximum of 8 temperature sensors, 2 set points per sensor: alarm/tripping) Measurement of phase and residual currents, measurement of 8 temperatures as an option A transformer may be equipped with specific integrated functions such as: Buchholz (detection of internal faults in immersed transformers) or DGPT/thermostat (detection of abnormal temperature/pressure). Sepam manages the alarm and tripping logic data supplied by the systems integrated in the transformer, for annunciation (signal lamp, message) and action (circuit breaker tripping).

12 变压器保护应用 Sepam T40/T42 保护功能:
50/51(相过流), 50N/51N(接地),46(负序不平衡), 50BF(断路器失灵) 49RMS(过负荷) 和 38/49T(温度监视) 27/59(欠/过压), 81L/81H(欠/过频) 67N/67NC, 方向性接地 -T42 67, 方向性相过流 -T42 I, U, P, E 测量 High-performing solutions for demanding transformer applications: - parallel transformer incomers (67) - isolated or compensated neutral (67N/67NC) Sepam T40/T42 type, - with directional protection functions 67N/67NC, 67, - with breaker failure protection function 50BF - with voltage and frequency protection functions 27/59, 81L/81H, 59N, 47 - with thermal overload protection function 49RMS 38/49T: temperature monitoring, based on the measurement of temperatures at different points in the transformer. (a maximum of 6 temperature sensors, 2 set points per sensor: alarm/tripping) Measurement of phase and residual currents, phase-to-neutral and residual voltages and 16 temperatures as an option A transformer may be equipped with specific integrated functions such as: Buchholz (detection of internal faults in immersed transformers) or DGPT/thermostat (detection of abnormal temperature/pressure). Sepam manages the alarm and tripping logic data supplied by the systems integrated in the transformer, for annunciation (signal lamp, message) and action (circuit breaker tripping).

13 变压器保护应用 Sepam T81/T82 全面的控制功能 (42I/23O) 保护功能:
50/51(相过流), 50N/51N(接地),46(负序不平衡),50BF(断路器失灵) 49RMS(过负荷) 和 38/49T(温度监视) 27/59(欠/过压), 81L/81H(欠/过频) 67N/67NC, 方向性接地-T81/T82 67, 方向性相过流-T82 64REF, 限制性接地故障 (接地电流差动保护) I, U, P, E 测量 Intelligent solutions for complete transformer applications: - parallel transformer incomers (67) - isolated or compensated neutral (67N/67NC) - large number of I/Os and logical equation editor => integral equipment control Sepam T81/T82 type, with the T40/T42 protection functions, plus: - 64REF: restricted earth fault, sensitive and fast protection against phase-to-earth faults on 3-phase windings with earthed neutral. - 27D: Positive sequence undervoltage, to detect insufficient or unbalanced network voltage - 27R: Remanent undervoltage, to allow the busbar supplying motors to be re-energized Measurement of phase and residual currents, phase-to-neutral and residual voltages, and 16 temperatures as an option A transformer may be equipped with specific integrated functions such as: Buchholz (detection of internal faults in immersed transformers) or DGPT/thermostat (detection of abnormal temperature/pressure). Sepam manages the alarm and tripping logical data supplied by the systems integrated in the transformer, for annunciation (signal lamp, message) and action (circuit breaker tripping).

14 变压器保护应用 Sepam T87 2卷变压器差动保护 87T (变压器差动), 防止相间短路 64REF, 防止相对地短路 其他保护功能:
50/51,50N/51N, 46,50BF 27/59, 81L/81H 49RMS 和 38/49T 24 (过激磁) 全面的控制功能(42I/23O) I, U, P, E 测量 Intelligent solutions for complete transformer applications: 2-winding transformer differential protection: - 87T : fast, sensitive and stable differential protection against phase-to-phase faults - 64REF: restricted earth fault, sensitive and fast protection against phase-to-earth faults on 3-phase windings with earthed neutral. - all other protection functions (50/51, 50N/51N, 49RMS, …) necessary as backup of the differential functions are available and performed by Sepam T87. - 24 : 过激磁, detection of overly high magnetic flux in the magnetic circuit of the transformer => temperature build-up and premature aging - large number of I/Os and logical equation editor => integral equipment control Measurement of phase and residual currents, phase-to-neutral and residual voltages, and 16 temperatures as an option A transformer may be equipped with specific integrated functions such as: Buchholz (detection of internal faults in immersed transformers) or DGPT/thermostat (detection of abnormal temperature/pressure). Sepam manages the alarm and tripping logical data supplied by the systems integrated in the transformer, for annunciation (signal lamp, message) and action (circuit breaker tripping).

15 电动机保护应用 Sepam M20 保护功能: 50/51(相过流), 50N/51N(接地)和46(负序不平衡)
49RMS(过负荷) 和 38/49T(温度监视) 特殊功能: 37, 相欠流 48/51LR, 超过起动时间和转子堵转 66, 每小时起动次数每小时起动次数每小时起动次数 Simple solution for common asynchronous motor applications. (mainly interests industrialists) Sepam M20 type: with the protection functions of Sepam T20 (against phase-to-phase and phase-to-earth short-circuits and overloads) with temperature monitoring (typically 1 temperature sensor per motor winding + bearing temperature, a maximum of 8 sensors, 2 set points per sensor: alarm/tripping) + specific protection functions to detect faults linked to the motor load: 37: phase undercurrent, for detection of and protection against no-load pump operation (pump priming loss leading to pump deterioration) 48: monitoring of motor starting conditions: starting time/current 51LR: rotor locking when in operation -> return to starting conditions 66: starts per hour (each start puts stress on the motor beyond its rated characteristics) Does not cause tripping of the contactor, but inhibition of closing when the limit has been reached.

16 电动机保护应用 Sepam M41 所有M20的保护功能, 加上: 67N/67NC, 方向性接地故障
32P, 32Q/40, 方向性有功和无功过功率 27/59, 欠电压/过电压 81L/81H, 欠频率/过频率 自动甩负荷 I, U, P, E 测量 High-performing solution for demanding motor applications (mainly interests industrialists): - isolated or compensated neutral (67N/67NC) - synchronous and asynchronous motors (32P, 32Q/40) Sepam M41 type, - with two-way protection functions 67N/67NC - with breaker failure protection function 50BF - with voltage and frequency protection functions 59, 81L/81H, 47 - with thermal overload protection function 49RMS - with protection functions for faults linked to motor load: 37, 48/51LR, /49T: temperature monitoring, based on the measurement of temperatures at different points in the motor (a maximum of 16 temperature sensors, 2 set points per sensor: alarm/tripping) 32P: reverse active power, for detection of synchronous and asynchronous motors operating as generators 32Q/40: reverse reactive power, for detection of loss of the excitation field on synchronous machines. (overheating of the rotor when the machine operates as an asynchronous one) 27D: positive sequence undervoltage 27R: remanent undervoltage to enable changeover/motor restarting ... Automatic load shedding associated with voltage (27D) and frequency (81L) protection functions Measurement of phase and residual currents, phase-to-neutral and residual voltages and 16 temperatures as an option

17 电动机保护应用 Sepam M81/M87/M88 保护功能: 50/51,50N/51N,46,50BF 49RMS 和 38/49T
27/59, 81L/81H, … 大型电动机保护: 37, 48/51LR, 66 32P, 32Q 67N/67NC 40 (失磁) 78PS (滑极/失步) 12/14 (电动机过速/欠速) 87M (电动机差动保护) 87T (电动机-变压器组差动保护) I, U, P, E 测量 Intelligent solutions for complete motor applications: (mainly interests industrialists): Sepam M81/M87/M88 type perform all the following protection functions: - motor protection against short-circuits: 50/51, 50N/51N, 67N/67NC - power supply fault protection: 46 - breaker failure protection function 50BF - voltage and frequency protection functions 27/59, 81L/81H, 47, 27D, 27R - thermal overload protection function 49RMS - RTD temperature monitoring 38/49T, based on the measurement of temperatures at different points in the motor (a maximum of 16 temperature sensors, 2 set points per sensor: alarm/tripping) - protection functions for faults linked to motor load: 37, 48/51LR, 66 - 32P: reverse active power, for detection of synchronous and asynchronous motors operating as generators - 32Q: reverse reactive power, for detection of loss of the excitation field on synchronous machines. (overheating of the rotor when the machine operates as an asynchronous one) - 40: field loss detected by underimpedance, for large machines on networks with low short-circuit power (local networks with generators) - 78PS: 滑极, protection against loss of synchronism on synchronous machines. 2 principles for unbalance (due to loss of synchronism) evaluation, equal-area criterion or number of power swings. - 12: overspeed, detection of machine racing or process monitoring - 14: underspeed, for process monitoring or zero speed detection

18 发电机保护应用 Sepam G40 保护功能: 50/51(相过流), 50N/51N(接地),46(负序不平衡), 50BF(断路器失灵)
49RMS(过负荷) 和 38/49T(温度监视) 27/59, 欠电压/过电压 81L/81H, 欠频率/过频率 特殊功能: 50V/51V, 电压限制性过流 32P, 32Q/40,方向性有功和无功过功率 I, U, P, E 测量 High-performing solution for protection of “small” generators: Sepam G40 type, - with breaker failure protection function 50BF - with voltage and frequency protection functions 59, 81L/81H, 47 - with thermal overload protection function 49RMS 38/49T: temperature monitoring, based on the measurement of temperatures at different points in the generator (a maximum of 16 temperature sensors, 2 set points per sensor: alarm/tripping) 50V/51V: overcurrent with voltage restraint, the current set point is lower when the network voltage decreases, to be sensitive to all types of external short-circuit currents even when the faulty current is lower than the generator rated current 32P: reverse active power, for detection of synchronous and asynchronous generators operating as motors 32Q/40: reverse reactive power, for detection of loss of the excitation field on synchronous machines. (overheating of the rotor when the machine operates as an asynchronous one) Measurement of phase and residual currents, phase-to-neutral and residual voltages and 16 temperatures as an option

19 发电机保护应用 Sepam G82/G87/G88 保护功能: 50/51,50N/51N,46,50BF 49RMS 和 38/49T
27/59, 81L/81H, … 全面的发电机保护: 50V/51V, 32P, 32Q, 67N 40 (失磁) 78PS (滑极) 12 /14 (发电机过/欠速) 21B (低阻抗) 50/27 (误上电) 64G (100% 定子接地) 24 (过激磁) 64REF (限制性接地故障) 87M (发电机差动保护) 87T (发电机-变压器组差动保护) Intelligent solutions for complete generator applications: Sepam G82/G87/G88 type perform all the following protection functions: - generator protection against short-circuits: 50/51, 50N/51N, 67N/67NC, 46 - breaker failure protection function 50BF - voltage and frequency protection functions 27/59, 81L/81H, 47, 27D, 27R - thermal overload protection function 49RMS - RTD temperature monitoring 38/49T - 50V/51V: overcurrent with voltage restraint, the current threshold is lower when the network voltage decreases, to be sensitive to all types of external short-circuit currents even when the faulty current is lower than the generator rated current - 32P: reverse active power, for detection of synchronous and asynchronous generators operating as motors Q: reverse reactive power, for detection of loss of the excitation field on synchronous machines. (overheating of the rotor when the machine operates as an asynchronous one) - 40: field loss detected by underimpedance, for large machines on networks with low short-circuit power (local networks with generators) - 78PS: 滑极, protection against loss of synchronism on synchronous machines. 2 principles for unbalance (due to loss of synchronism) evaluation, equal-area criterion or number of power swings. - 12: overspeed, detection of machine racing or process monitoring - 14: underspeed, for process monitoring or zero speed detection - 21B: underimpedance, to detect phaase-to-phase short-circuits (backup of 50/51) - 50/27: inadvertant energization, checks the generator starting sequence, with an instantaneous phase overcurrent protection (50) confirmed by a time-delayed undervoltage (27) - 64G: 100% stator earth fault, to protect generator with earthed neutral and step-up transformer against earth fault. 64G = 59N + 27TN: 59N protects 80% of the stator winding, terminal end, 27TN, 3rd harmonic undervoltage, protects 20% of the stator winding, neutral point end - 24: 过激磁, detection of overly high magnetic flux in the magnetic circuit of the generator => temperature build-up and premature aging

20 母线保护应用 Sepam B21/B22 电压和频率保护功能: 27/59, 欠电压/过电压 27S, 相欠电压
59N, 中性点电压偏移(绝缘监视) 81L/81H, 欠/过频 27D/47, 正序欠电压和相旋转方向 27R, 剩余欠电压 81R, 频率改变率-B22 U电压测量 Simple solution for common busbar applications: network voltage and frequency monitoring (measurement of phase-to-neutral and residual voltages by VT) Sepam B21 type: Protection functions used to detect and indicate abnormal substation supply. One B21 per substation may be sufficient. Corrective actions (inhibition, changeover/load shedding based on min., generator correction according to min./max.) not performed by Sepam but by dedicated systems! 27/59: phase-to-phase under/overvoltage, to monitor network voltage. 27S: phase-to-neutral undervoltage, to detect the loss of a phase, or to identify the phase with an earth fault (on isolated neutral networks) 59N: neutral voltage displacement, to detect/indicate earth faults on isolated neutral networks 81L/81H: under/overfrequency, for network frequency monitoring Protection functions used to monitor motor supply: 27D: positive sequence undervoltage 47: checking of phase rotation direction, based on calculation of positive sequence voltage and linked to function 27D. 27R: remanent undervoltage, to enable changeover/motor restarting …

21 母线保护应用 Sepam B80 进线保护带一个额外的电压检测 50/51,50N/51N,46,50BF
27, 59, 59N, 81L, 81H 27D, 47, 27R 测量 3 相电压(进线) 1 个相电压(母线上),检查进线或母联合闸前母线上的剩余电压 全面的控制功能 (42I/23O) I, U, P, E 测量 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

22 母线保护应用 Sepam B83 完整保护功能,针对两段母线 50/51,50N/51N,46,50BF
27, 59, 59N, 81L, 81H 27D, 47, 27R 两段母线的测量 3个相电压 剩余电压 全面的控制功能 (42I/23O) I, U, P, E 测量 Sepam B83 A three-in-one application by combining: - the 50/51 protection functions for coupling (S20), - and voltage protection functions for the two 1/2 busbars (2 x B21). Caution. The 81R function is not available with the B83 and it is therefore not possible, using Z8x, to create a relay with the 81R function for the additional voltage channels.

23 电容器保护应用 Sepam C86 电容器组的保护,分4步,三角形或双星形排列 保护功能: 50/51, 50N/51N, 46, 50BF
27, 59, 81L, 81H, 等。 特别功能: 51C, 电容器组不平衡 49RMS 电容器组投切控制 I, U, P, E, C 测量 Sepam C86

24 Sepam 保护继电器, 格守精准定律, 引领方向如一!
功能选型 模块化结构 产品特点 方案与应用 2

25 Sepam 模块化结构 功能可由选装模块的增加而增强 特别适合您的需要 随您的安装而逐步扩展

26 逻辑输入/输出模块 Sepam 20/40 系列 附加的逻辑输入/输出模块 Sepam本体带4 个基本的继电器输出 可由一个扩展模块增加
10 个逻辑输入 4 个继电器输出 根据逻辑输入电压分为三种类型 MES114: 24V~250V DC MES114E: 110V AC/DC MES114F: 220V AC/DC 3 types of MES114 modules with 10 logic inputs / 4 relay outputs: - MES114: 24 to 250 V DC, with typical switching threshold = 14 V DC - MES114E: 110 to 125 V DC, with typical switching threshold = 75 V DC and 110 V AC inputs, with typical switching threshold = 82 VAC - MES114F: 220 to 250 V DC, with typical switching threshold = 137 V DC and 220 VAC, with typical switching threshold = 154 VAC To add I/Os: - mount the MES114 module on the base unit when you want (can be upgraded over time) - declare the module by Sepam parameter setting - the functions related to the new I/Os are operational! (standard functions, with no need for programming or particular customization!)

27 逻辑输入/输出模块 Sepam 80系列 附加的逻辑输入/输出模块 (MES120) Sepam 80本体上有5个基本继电器输出口
可由附加的模块扩展 14个逻辑输入 ( V DC) 6个继电器输出 最多3个模块 MES120 module with 14 logic inputs / 6 relay outputs: - 14 inputs 24 to 250 V DC, with typical switching threshold = 14 V DC 4 independent isolated inputs, 2x5 common point inputs - 1 control relay output and 5 indication relay outputs To add an I/O module (3 module max.) - mount the MES114 module on the base unit when you want (can be upgraded over time) - declare the module by Sepam parameter setting - the functions related to the new I/Os are operational! (standard functions, with no need for programming or particular customization!)

28 温度传感器模块 Sepam 20/40/80 系列 可更好地保护变压器,电动机和发电机 温度传感器远端模块 (MET148-2)
可连接 Pt100, Ni100 或 Ni120 温度传感器 可更好地保护变压器,电动机和发电机 Sepam 20系列 : 可连接1个模块 / 8 个温度量 输入 Sepam 40系列 : 可连接2个模块 / 16 个温度量 输入 Sepam 80系列 : 可连接2个模块 / 16 个温度量 输入 Remote MET148-2 module in LV compartment, not on motor, generator or transformer. - Sepam T20 and M20: connection of 1 MET148-2 module max. for measurement of 8 temperatures - Sepam T40, T42, M41 and G40: connection of 2 MET148-2 modules max. for measurement of 16 temperatures 8 RTDs of the same type (Pt100, Ni100 or Ni120) can be connected to one MET module. Temperature sensor monitoring: - sensors not connected or short-circuited - only sensors actually connected/used are monitored - RTD fault alarm message on UMI / communication

29 模拟量输出模块 Sepam 20/40/80 系列 可远程传输测量值 1 个模拟量输出远端模块 (MSA141)
0-10mA, 0-20mA 或 4-20mA 可远程传输测量值 - For remote display of a measurement, to be chosen among the measurements made by Sepam - Allows a savings of 1 CT winding dedicated to metering in certain cases.

30 通讯接口模块 Sepam 20/40 系列 可连接1个通讯接口 适合于 2线 RS 485 (ACE949-2)
- Modbus protocol embedded in the Sepam base unit - Communication implemented by means of a compulsory connection interface, ACE949-2 for connection to a 2-wire RS485 bus ACE959 for connection to a 4-wire RS485 bus ACE937 for connection to fiber optic network (star topology) - ACE949-2 and ACE959 to be supplied with 12 V DC or 24 V DC - All the accessories for fast, dependable implementation are available

31 通讯接口模块 Sepam 80系列 可最多连接2个通讯接口 适合于 2线 RS 485 (ACE949-2)
- 2 independent communication ports, for Sepam integration in multi-master or redundant architectures - Modbus protocol embedded in the Sepam base unit - Communication implemented by means of a compulsory connection interface, ACE949-2 for connection to a 2-wire RS485 bus ACE959 for connection to a 4-wire RS485 bus ACE937 for connection to fiber optic network (star topology) - ACE949-2 and ACE959 to be supplied with 12 V DC or 24 V DC - All the accessories for fast, dependable implementation are available

32 同步校验模块 Sepam 80 系列 MCS025远端同步校验模块 适用于变电站进/出线,变压器,发电机和母线应用
可测量两组相对零或相对相电压 检查两个网络中的电压,频率和相角 通过3个继电器输出控制闭合断路器以允许并列 SFT2841 software Unavoidable software tool, standard tool for all Sepam users! More detailed presentation at the end of the presentation. SFT2826 software To display and analize disturbance data recorded by Sepam.

33 软件工具 Sepam 20/40/80 系列 Sepam 软件工具 SFT2841软件, 为 Sepam 参数设定 保护整定值设定 本地操作
SFT2841 software Unavoidable software tool, standard tool for all Sepam users! More detailed presentation at the end of the presentation. SFT2826 software To display and analize disturbance data recorded by Sepam.

34 模块配置 - Sepam 20系列 + + + + + + + + 1. 基本功能: 保护功能及测量功能详见Sepam选型表。
Sepam S20/T20/M20 MES114 ACE949-2 MSA141 + + + MET148-2 (适用于T20/M20) + + + + + 基本功能:保护,测量… 监控功能 通讯功能 温度测量 模拟量输出 1. 基本功能: 保护功能及测量功能详见Sepam选型表。 2. 监控功能:使用MES114模块可增加10个开关量输入和4个继电器接点输出。开关量输入可监视开关柜断路器分合闸位置、跳闸回路断线、温度/瓦斯保护、工作/试验位置、储能弹簧位置及接地开关位置等,继电器接点输出可用于开关动作输出或信号输出。 3. 通讯功能:ACE949-2模块实现2线RS485串行通讯功能。 4. 温度测量:使用MET148-2模块可连接铂电阻(Pt100),实现温度测量及温度设定,仅适用于Sepam T20或M20。 5. 模拟量输出:使用MSA141模块可将某个测量值转换为模拟量信号(4~20mA, 0~10mA或0~20mA)输出. Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

35 模块配置 - Sepam 40系列 + + + + + + + + 1. 基本功能: 保护功能及测量功能详见Sepam选型表。
Sepam S40/S41/S42/T40/T42/M41/G40 MES114 ACE949-2 + MSA141 + + + MET148-2 (适用于T40/T42/M41/G40) + + + + 模拟量输出 基本功能:保护,测量… 监控功能 通讯功能 温度测量 1. 基本功能: 保护功能及测量功能详见Sepam选型表。 2. 监控功能:使用MES114模块可增加10个开关量输入和4个继电器接点输出。开关量输入可监视断路器分合闸位置、跳闸回路断线、温度/瓦斯保护、工作/试验位置、储能弹簧位置及接地开关位置等,继电器接点可用于开关动作输出或信号输出。 3. 通讯功能:ACE949-2模块实现2线RS485串行通讯功能。 4. 温度测量:使用MET148-2模块,可连接铂电阻(Pt100),实现温度测量及温度设定,仅适用于Sepam T40、T42、M41或G40,可连接2个MET148-2模块。 5. 模拟量输出:使用MSA141模块可将某个测量值转换为模拟量信号(4~20mA, 0~10mA或0~20mA)输出. Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

36 Sepam S80/S81/S82/S84/T81/T82/T87/M81/M87/M88/G82/G87/G88/C86/B80/B83
MCS025 (仅适用于S8x, T8x,G8x或B8x) Sepam S80/S81/S82/S84/T81/T82/T87/M81/M87/M88/G82/G87/G88/C86/B80/B83 MES120 最多3个 + ACE949-2 最多2个 + + + MET148-2 (仅适用于T8x, M8x和G8x) + MSA141 基本功能: 保护,测量… + + + + + 监控功能 通讯功能 温度测量 模拟量输出 同步校验 1. 基本功能: 保护功能及测量功能详见Sepam选型表。 2. 监控功能:使用MES120模块可增加14个开关量输入和6个继电器接点输出。开关量输入可监视开关柜断路器分合闸位置、跳闸回路断线、温度/瓦斯保护、工作/试验位置、储能弹簧位置及接地开关位置等,继电器接点可用于开关动作输出或信号输出。 3. 通讯功能:ACE949-2模块实现2线RS485串行通讯功能。 4. 温度测量:使用MET148-2模块可连接铂电阻(Pt100),实现温度测量及温度设定,适用于Sepam T8x、M8x或G8x,可连接2个MET148-2模块。 5. 模拟量输出:使用MSA141模块可将某个测量值转换为模拟量信号(4~20mA, 0~10mA或0~20mA)输出. 6. 同步校验:使用MCS025模块可检测两路电源是否同步,适用于S8x,T8x,G8x或B8x. Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

37 Sepam 保护继电器, 格守精准定律, 引领方向如一!
功能选型 模块化结构 产品特点 方案与应用 2

38  Sepam 系列, 稳定和可靠 得益于超过20年的Sepam系列产品经验 基于可靠性研究设计:
FMECA: 故障模式, 影响和临界状态分析 故障率的计算 质量保证基于全面的生产阶段的检查 获得国际标准和认证;以及中国监测机构认证; More than 20 years of experience: Sepam 15 was born in 1985, 1st multifunctional digital protection unit Total Sepam sales: more than 100,000! (Sepam 15/1000/2000 and Sepam series20, series 40 and series 80) Already more than 25,000 Sepam , present production: 1300 per month Dependability study to reduce as much as possible the risks of unwanted tripping failure to trip when a fault occurs The conclusions of the study systematically determine the design and development of every component of the Sepam range. A dependability study includes the following, as a minimum: - FMECA (Failure Mode, Effects and Criticality Analysis) which is used to predict the consequences of a component failure on the operation of the protection, - calculation of the predicted failure rates of the electronic components included in the protection. This calculation is used to quantify the risk of the appearance of unwanted problems. Illustration: page of Relex software, used to calculate predicted failure rates of electronic components based the reliability data compendium: Military Handbook 217 (MIL HDBK 217). - Continuous self-testing to monitor the protection unit and its different modules. Switching to fail-safe position in case of failure (all outputs forced to 0), with indication by watchdog logic output. 508

39 逻辑编程 Sepam 40/80系列 可改变 Sepam的功能适合您的要求! 包含在 SFT2841软件工具中
逻辑运算符 NOT (非) , AND (与), OR (或), XOR (异或), 定时器, 闭锁继电器, 可编程定时脉冲 逻辑输入和保护数据 Sepam series 40/80: a logical equation editoris integrated in SFT2841 and can be used to complete and adapt the standard control functions to solve some tricky cases. (The comprehensive programming of control functions as with Logipam on Sepam 2000 is not allowed.) With series 40 series 80 Maximum number of operations = with the following operators: - Logical operators AND, OR, XOR and NOT + bistables elements SR, with priority to SET and LATCH, bistable element with reset by action on the “Reset” key on UMI - timers, Ton or Toff or programmable pulse Equation input variables: logic inputs and all outputs of the prtection functions: instantaneous, time-delayed outputs, faulty phase, ... - local variables, saved VLx local variables, not saved VVx Modbus remote control orders (TC) output variables Vx to be assigned in the control matrix to logic outputs, LEDs or advanced UMI messages associated with the circuit breaker control function indicated in the control room via the communication link Pre-assigned outputs to control functions: CB control, recloser or disturbance recording, etc ...

40 逻辑编程 Sepam 40/80系列 自动转换装置 电动机起动顺序 减负载 对中压柜外部设备的管理 等等.

41 自动电源转换功能 根据用户要求编制逻辑程序 可选多种闭锁条件 多种切换方式选择 ATS S80 S80 S80 S80
Simple solution for common substation applications: protection of cable incomers and feeders or substation lines Sepam S20 type, with the following protection functions: 50/51: protection against phase-to-phase short-circuits (see "performance" for details) 50N/51N: protection against phase-to-earth short-circuits (see "performance" for details) 46: protection against phase unbalance (or phase loss) which causes overheating and deterioration of the equipment supplied Measurement of phase currents and residual current Logic discrimination: used to reduce fault (short-circuit) tripping time and thereby reduce the consequences. Discrimination principle based on the exchange of logic data between downstream and upstream protection units 4-cycle recloser: interests energy distributors rather than industrialists, to eliminate transient faults affecting overhead lines. -> Reduction of breaking time

42 自动转换复归 根据用户要求编制逻辑程序 可选多种闭锁条件 多种切换方式选择 S80 S80 S80 S80

43 开关柜诊断 故障跳闸次数 分闸时间 储能时间 累计分断电流, 总值和故障电流分级 可作为有效的预防性维护! 连续的, 全面的分断设备监视:
Especially enhanced switchgear diagnosis functions, derived from =SE='s experience as a manufacturer, to facilitate preventive maintenance of the breaking device: - trip circuit supervision: detects fault wiring between Sepam and switchgear trip unit - number of operations - operating time: measurement of the breaking device’s opening and closing times in ms (typically between 50 and 100ms, please refer to manufacturer characteristics) if that time increases: downgrading of protection performances (increase in the duration of the fault), mechanical checking of the breaking device to be planned! - charging time: measurement of the breaking device operating mechanism charging time, in the case of operating mechanism charging by an electric motor, as soon as the circuit breaker is closed (in the range of 10 s, please refer to manufacturer characteristics, essential if recloser is used) if the time increases: sign of motor downgrading, charging time becomes incompatible with reclosing cycle, checking / replacement of the breaking device’s electrical operating mechanism to be planned! - Cumulative breaking current: counted according to 5 levels of fault current - SF6 pressure switch: all information of interest for switchgear maintenance!

44 网络辅助诊断 更好地故障分析! 扰动记录(故障录波) 以COMTRADE格式保存1 到 19 个记录 最大记忆时间: 42s
每周期最大采样点: 36 可对逻辑输入/输出口进行录波 相不平衡 跳闸电流 历史报警 跳闸信息 更好地故障分析! Analysis of failures occurring on your electrical network based on diagnosis information available in Sepam: - Disturbance recording: Local recovery of records or recovery via communication link, for restoring and event analysis: checking of tripping times (protection unit and switchgear), wave form analysis, determination of faulty phases … COMTRADE file compatible with SFT2826 and with simulation tool, used to accurately reproduce the event for more in-depth expert appraisal. series 20: 2 records of 86 periods triggered by parameterizable event. Recording of a maximum of 4 analog values (3I+Io or 3V+Vo, sampling of 12 points per period) and 10 logic inputs series 40: 20 s of records, distributed between 1 (10s) event and 19 (1s) events (parameter), or n t-second events, according to the formula: (n+1).t <= 20s Recording of a maximum of 8 analog values (sampling of 12 points per period), 10 logic inputs, O1 to O4, pickup + 1 series 80: 42 s of records max to record 1 to 19 events of 1 to 20 s, according to network frequency and sampling frequency. Recording of all analog values (sampling of 12 or 36 points per period), and all I/Os - TripI1, tripI2, tripI3, tripI0 stored each time tripping occurs. - Phase unbalance, generating heat (losses and deterioration) - Alarm history: series 20: last 64 alarms stored, available on PC with descriptions + date + time/mn/s and descriptions of the last 16 alarms available on advanced UMI series 40: last 250 alarms stored and saved, available on PC with descriptions + date + time/mn/s + faulty phase. The last 16 alarms are available on the advanced UMI with the same information. - Tripping context, for all Sepam series 40: recording of all measurements with date / time for the last 5 trips, saved and available on advanced UMI and on PC

45 远程操作 2线/4线RS485总线或光纤通讯 最大传输速率: 38400 波特率,响应时间 < 15 ms 所有数据均可通讯 时标事件
具有«操作前选择» 方式的可靠的遥控命令 扰动记录 远端保护整定 ALL the data in Sepam may be read by a centralized monitoring and control system time-tagged events: 1 millisecond resolution, available in 2 different tables, synchronization of Sepam clocks via communication link or by signal on logic input - disturbance recording records - 64 remote annunciation bits for alarms, reports, logic inputs, etc... - reading of protection settings In write mode: - 16 remote control bits, inhibited in local mode: in direct mode or in «select before operate (SBO)» mode: order executed after 2-stage writing of 2 remote control bits - remote setting of protection functions, function inhibited by parameter setting if the user wishes.

46 多种通讯规约 变电站内部 ModBus RTU IEC 60870-5-103 DNP3 变电站和 SCADA
Ethernet Modbus TCP/IP

47 通讯网络 S-LAN (监控主站) 监控通讯网络 用于监视和控制,信号输出和报警 E-LAN (工程师站) 维护通讯网络用于: 诊断
检查设定值 查看事件和故障录波

48 双通讯口 Sepam 80系列 两个独立的 Modbus 通讯口 可集成在两个不同的通讯网络中 适用于通讯网络冗余
可经由SFT2841在 Modbus通讯网络上对Sepam 80系列进行简单的整定和操作: 全面的Sepam参数和保护整定 定制的Sepam功能 历史报警 Sepam series 80 only

49 以太网连接和Web服务器 可将Sepam集成在您的以太网络上 EGX 以太网/Modbus网关 Modbus / TCP/IP 多主机协议
快速传输速率 可简单地从Sepam获取数据 从一个具有internet/intranet浏览器的计算机上 可由包含在EGX网关上的网页上给出 以太网 以太网/Modbus网关 2 Ethernet / Modbus gateways proposed in the PowerLogic System offer: - ECC, integrated in CM4000, with 1 RS485 Modbus port for 32 slaves - EGX, stand-alone, with 2 RS485 Modbus ports for 2x32 slaves Gateway function between SCADA on Ethernet network (Modbus masters) and Sepam slaves on RS485 Modbus network Webserver function: gateways with 6 HTML pages, 5 of which are customizable - to group together basic data / measurements from the slaves - accessible from any PC on Ethernet with an Internet Explorer type browser. 在RS485 Modbus网络上的Sepam

50 本体易于安装 减少安装限制: 紧凑的, 轻巧的设计, 减少了安装厚度 < 100 mm (20/40系列)
端子和连接器带铭刻的端子号 可在无任何预防措施的情况下插拔(避免CT开路) - Reduced depth: very interesting for revamping projects! - Front panel cutout (simple rectangular shape): Sepam series 20/40 with same dimensions as Sepam 1000: Sepam series 80 with same dimensions as compact Sepam 2000 (S2026) => interesting for substitution of existing Sepam 1000/2000, and for =SE= LAUs - No parameter setting of microswitches - Connection of either 1A or 5A CT with no distinction! Same wiring of the CCA630 whatever the CT, better than the competitors!

51 可被所有人理解 ... ... 具有各种语言! 国内唯一全系列汉化的 进口保护装置! 屏幕语言可选为中文 提供各种图形: 印刷体字符 图画
可选英文 Customer advantages: - Clarity, puts itself at the facility manager’s level - Time saved during servicing Sepam series 40/80: creation of 30 customized advanced UMI messages, by use of SFT2841 Advanced UMI local customization: - According to local marketing strategy, local customization under local responsibility, to be positively reinforced and sold! - Translation of screen backgrounds and fault messages, with software tool SFT2840 - Manufacturing of local version with software SFT2842, allowing local adaptation of Sepam 国内唯一全系列汉化的 进口保护装置!

52 Sepam 保护继电器, 格守精准定律, 引领方向如一!
功能选型 模块化结构 产品特点 方案与应用 2

53 进线保护应用方案 单进线保护 无电压和频率监测 母线电压和频率监测 进线电压和频率监测 带有附加母线电压监测的进线保护
甩负荷: 基于低周(81L)和频率滑差(81R) Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

54 进线保护应用方案 双进线保护 平行进线保护 单母线带有自动电源切换 单母线分段带有自动电源切换 单母线分段带有自动电源切换(附带检同期功能)
带有方向性过流(67)和方向性接地保护(67N) Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

55 进线保护应用方案 双进线保护 平行进线保护 单母线带有自动电源切换 单母线分段带有自动电源切换
带有方向性过流(67)和方向性接地保护(67N) Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

56 馈线保护应用方案 在阻抗接地或中性点直接接地系统中对低容性馈线的保护 在阻抗接地、补偿或不接地系统中对高容性馈线的保护 无电压和频率监测
有电压和频率监测 在阻抗接地、补偿或不接地系统中对高容性馈线的保护 带方向性接地保护(67N/67NC) Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

57 母线保护应用方案 电压监测(适用于PT监测和保护) 母线断路器保护:带有母线短路保护及电压和频率监测功能 母线三相电压和中性点电压的监测
带有甩负荷功能的母线三相电压和中性点电压的监测:基于低周(81L)和频率滑差(81R) 母线断路器保护:带有母线短路保护及电压和频率监测功能 带有母线短路保护 带有母线短路保护和电压监测 母线短路保护,监测2段母线的三相电压和中性点电压 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

58 变压器保护应用方案 配电变压器保护 (变压器短路和热过载保护;变压器非电量保护:温度、瓦斯及压力;RTD温度监测) 无电压监测的变压器保护
一次侧接地故障保护 中性点接地故障保护 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

59 变压器保护应用方案 配电变压器保护 (变压器短路和热过载保护;变压器非电量保护:温度、瓦斯及压力;RTD温度监测) 有电压监测的变压器保护
一次侧接地故障保护 一次侧接地故障保护,机壳接地漏电保护 一次侧及二次侧中性点接地故障保护 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible. 注意:对于距离较长的馈线可使用方向性接地保护(67N/67NC)功能

60 变压器保护应用方案 110KV及以下主变压器保护(差动主保护、后备保护及非电量保护) Sepam T87(差动、后备及非电量综合保护)
一次侧接地故障保护 一次侧接地故障保护,二次侧中性点接地 一次侧及二次侧中性点接地故障保护 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

61 变压器保护应用方案 110KV及以下主变压器保护(差动主保护、后备保护及非电量保护)
Sepam Z82 + Sepam Txx(差动主保护 + 后备及非电量保护) 一次侧接地故障保护 一次侧接地故障保护,二次侧中性点接地 一次侧及二次侧中性点接地故障保护 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

62 电动机保护应用方案 电动机保护 (短路保护、接地保护、起动监视、转子堵转、温度监视及相欠流保护) 无电压监测的电动机保护 直接起动
自耦变压器起动 两路电源 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

63 电动机保护应用方案 电动机保护 (短路保护、接地保护、起动监视、转子堵转、温度监视及相欠流保护) 有电压监测的电动机保护 直接起动
自耦变压器起动 两路电源 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

64 电动机保护应用方案 电动机保护 (短路保护、接地保护、起动监视、转子堵转、温度监视及相欠流保护) 有电压监测的电动机保护 直接起动
自耦变压器起动 自平衡差动 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

65 电动机保护应用方案 变压器-电动机组保护 (短路保护、接地保护、起动监视、转子堵转、温度监视及相欠流保护) 无电压监测 有电压监视
有变压器监视功能 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible. 可实现变压器一次侧接地保护 需通过其他设备监视电动机绝缘状况 可实现变压器一次侧接地保护 通过中性点电压偏移 (59N)保护功能监视电动机绝缘状况 变压器监视:温度、瓦斯保护

66 电动机保护应用方案 变压器-电动机组保护 (差动保护、短路保护、接地保护、起动监视、转子堵转、温度监视及相欠流保护)
Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible. 可实现变压器一次侧接地保护 电动机接地故障保护 可实现变压器一次侧接地保护 通过中性点电压偏移 (59N)保护功能监视电动机绝缘状况

67 发电机保护应用方案 单个发电机保护 (电压限制性相过流保护、短路保护、接地保护、方向性有功和无功保护、过负荷及温度监视) 一点接地保护
一点接地和绝缘监视保护 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible. 直接检测接地电流(50G/51G) 直接检测接地电流(50G/51G) 通过中性点电压偏移 (59N) 监视发电机绝缘状况

68 发电机保护应用方案 连接至其他电网或发电机的发电机保护 (电压限制性相过流保护、短路保护、接地保护、100%定子接地、方向性相过流和接地保护、方向性有功和无功保护、低阻抗、误送电、失磁、失步、过负荷及温度监视等…) 一点接地和绝缘监视保护 100%定子接地保护 一点接地和绝缘监视保护 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible. 直接检测接地电流(50G/51G) 通过中性点电压偏移 (59N) 监视发电机绝缘状况 限制性接地故障 接地故障

69 发电机保护应用方案 发电机差动保护 自平衡差动 发电机差动保护(87M) Sepam B80
The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

70 发电机保护应用方案 发电机-变压器组保护 单个发电机-变压器组 连接至其他电网或发电机的保护 Sepam B80
The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

71 发电机保护应用方案 发电机-变压器组保护 发电机-变压器组差动 Sepam B80
The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

72 电容器保护应用方案 单组电容器保护 无电压监测的电容器组(三角形连接) 有电压监测的电容器组(三角形连接) 电容器组短路保护
电容器组短路保护;电压和频率监测;过负荷保护(C86) Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

73 电容器保护应用方案 1~4组电容器保护(双星形连接) 电容器组短路保护 电压和频率监测 过负荷保护 中性点补平衡保护(电流横差)
Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

74 10KV单母线双进线应用方案 - Sepam 20/40系列
Sepam T20 + MES ACE949-2 Sepam M20 + MES ACE949-2 Sepam S40 + MES ACE949-2 Sepam S40 + MES ACE949-2 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible. 注: 进线使用Sepam S40可实现双路电源的备自投功能。

75 10KV单母线双进线应用方案 - Sepam 20 /40系列
Sepam T20 + MES ACE949-2 Sepam M20 + MES ACE949-2 Sepam S40 + MES ACE949-2 Sepam S20 + MES ACE949-2 Sepam S40 + MES ACE949-2 Sepam T20 + MES ACE949-2 Sepam M20 + MES ACE949-2 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible. 注: 进线使用Sepam S40可实现双路电源的备自投功能。

76 10KV单母线双进线应用方案 - Sepam 40系列
Sepam T40 + MES ACE949-2 Sepam M41 + MES ACE949-2 Sepam S40 + MES ACE949-2 Sepam S40 + MES ACE949-2 Sepam S40 + MES ACE949-2 Sepam T40 + MES ACE949-2 Sepam M41 + MES ACE949-2 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible. 注: 进线使用Sepam S40可实现双路电源的备自投功能。 所有进/线回路均可实现电压、电流、功率、电能、功率因数、频率等电气参数测量。

77 10KV单母线双进线应用方案 - Sepam 80系列
Sepam T87 + MES ACE949-2 Sepam M87 + MES ACE949-2 Sepam S MES ACE949-2 Sepam S MES ACE949-2 Sepam S MES ACE949-2 Sepam T MES ACE949-2 Sepam M MES ACE949-2 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible. 注: 进线使用Sepam S80可实现双路电源的备自投功能。 所有进/线回路均可实现电压、电流、功率、电能、功率因数、频率等电气参数测量。 Sepam T87可实现双卷变压器差动功能;Sepam M87可实现电动机差动功能。

78 35KV应用方案 Sepam T87 Sepam T87 差动保护 差动保护 Sepam T40 Sepam T40 后备保护 后备保护
Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

79 110KV应用方案 Sepam S80 Sepam S80 线路测控单元 线路测控单元 Sepam S80 Sepam S80 进线保护
Sepam T87 Sepam T87 差动保护 Sepam S80 Sepam S80 变压器测控单元 变压器测控单元 Sepam T40 Sepam T40 后备保护 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

80 通讯应用方案 单机串口通讯 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.

81 通讯应用方案 以太网通讯 Sepam B80 The remanent voltage on the busbars is caused by the remanent voltage produced by motors for approximately 100 ms following disconnection (longer for synchronous motors and capacitors). The check on the remanent voltage avoids closing the incomer circuit breaker for the necessary period. Presence of remanent voltage when the motors are re-energized can seriously damage the motors. Sepam B80 can also be used ins the same way as B83, in which case only one voltage is measured on the two 1/2 busbars and the 59N protection function is not possible.